Electrical wire Code chart




Table for Control electrical wire
Assign electrical cable color from following table

Conductor # First Tracer ColorSecond Tracer Color
1 Black---
2Red---
3Blue---
4Orange---
5Yellow---
6 Brown---
7 RedBlack
8 BlueBlack
9OrangeBlack
10YellowBlack
11 BrownBlack
12BlackRed
13 BlueRed
14 OrangeRed
15 YellowRed
16 BrownRed
17 BlackBlue
18 RedBlue
19 OrangeBlue
20 YellowBlue
21 BrownBlue
22BlackOrange
23 RedOrange
24BlueOrange
25 YellowOrange
26BrownOrange
27 BlackYellow
28 RedYellow
29BlueYellow
30 OrangeYellow
31BrownYellow
32BlackBrown
33 RedBrown
34BlueBrown
35OrangeBrown
36 YellowBrown






480 V AC

Phase A = Brown
Phase B =Orange
Phase C = Yellow
Ground = Green

120 V AC

Hot = Black
Neutral = White
Control = Red
Ground = Green

24 V DC

Positive = Blue
Negative = Yellow
Control = Orange
Ground = Green








Determine cable size

Determine electrical wire size using table 310.16 NEC2008 on page 70-148. Simply calculate amperage (current) flow through the circuit and then apply the table.

How to calculate current? In practice, we can find out power (W) and voltage (V) of equipments through vendor information. Based on this vendor information,we'll be knowing exactly how to power the equipment. If we lack of this basic knowledge, it is so dangerous.
For example, power a 120V pump through a 220V voltage source; you will burn out the pump.
Knowing power and voltage, current can be determined. See electrical formulas.
Be careful to apply the appropriate one phase or three phase formulas. Be plan in advance whether you will wire equipment at line to neutral or line to line voltage source.
V L-L=1.73* V L-N

Table 316.16

SIZE AWG OR KCMIL COPPER COPPER COPPER ALUMINUM ALUMINUM ALUMINUM SIZE AWG OR KCMIL
_ TYPE TW,UF TYPES RHW
,THHW,THW,
THWN,XHHW
USE,ZW
RHW-2,THHN
THHW,THW-2
(90°C)
TYPES TW,UF
(60°C)
TYPES RHW
THHW,THW
THWN,XHHW
USE
TYPES TBS,SA
SIS,THHW
SIZE AWG OR KCMIL
18
16
14
12
10
8
_
_
20
25
30
40
_
_
20
25
35
50
14
18
25
30
40
55
_
_
_
20
25
30
_
_
_
20
30
40
_
_
_
25
35
45
_
_
_
12
10
8
6
4
3
2
1
55
70
85
95
110
65
85
100
115
130
75
95
110
130
150
40
55
65
75
85
50
65
75
90
100
60
75
85
100
115
6
4
3
2
1
1/0
2/0
3/0
4/0
125
145
165
195
150
175
200
230
170
195
225
260
100
115
130
150
120
135
155
180
135
150
175
205
1/0
2/0
3/0
4/0
250
300
350
400
500
215
240
260
280
320
255
285
310
335
380
290
320
350
380
430
170
190
210
225
260
205
230
250
270
310
230
225
280
305
350
250
300
350
400
500
600
700
750
800
900
335
385
400
410
435
420
460
475
490
520
475
520
535
555
585
285
310
320
330
335
340
375
385
395
425
385
420
435
450
480
600
700
750
800
900
1000
1250
1500
1750
2000
435
495
520
545
560
545
590
625
650
665
615
665
705
735
750
375
405
435
455
470
445
485
520
545
560
500
545
585
615
630
1000
1250
1500
1750
2000


Assume the current calculated result is 14A, electrical wire type is copper THHN, insulated conductors rated at 90° C, and so based on the table, wire size is 18 AWG. For practical safety application, recommended power wire size should be bigger than 12 AWG.





Reference

National Electrical Code 2008
IEEE- Institute of Electrical and Electronics Engineers



Job Listings

AtlantaMinneapolisSt Louis
AustinNewyorkTampa
BaltimoreOrlandoWashington
BostonPhiladelphiaBy Keywords
CanadaPhoenixCivil Engineering
CharlottePortlandEngineering
ChicagoRaleighIndustrial Engineering
DallasRichmondInformation Technology
DenverSacramentoManufacturing Engineering
DetroitSalt lake CityMechanical Engineering
Houston San DiegoElectrical Engineering
Kansas CitySeattleSoftware Engineering
Los AngelesSilicon ValleyTelecom Engineering

Back to Home Page - Electrical Wire