Determine conduit size:
conduit size
The rigid metal conduit sizing is determined by using table C.8 NEC 2008 on page 70-739. Do these steps 1. (Find cable size) 2. Apply following table Conductor size (AWG/ Kcmil) | MD (TD)
16 (1/2) | MD (TD)
21 (3/4) | MD (TD)
27 (1) | MD (TD)
35 (11/4) | MD (TD)
41 (11/2) | MD (TD)
53 (2) | MD (TD)
63 (21/2) | MD (TD)
78 (3) | MD (TD)
91 (31/2) | MD (TD)
103 (4) | MD (TD)
129 (5) | MD (TD)
155 (6) | 14 12 10 8 6 | 4 3 3 1 1 | 7 6 5 2 1 | 12 10 8 4 3 | 21 17 14 7 6 | 28 23 19 10 8 | 46 38 31 16 13 | 66 55 44 23 18 | 102 85 68 36 29 | 136 113 91 48 38 | 176 146 118 61 49 | 276 229 185 87 77 | 398 330 267 139 112 | 4 3 2 1 | 1 1 1 0 | 1 1 1 1 | 2 2 1 1 | 4 4 3 1 | 6 5 4 3 | 10 9 7 5 | 14 12 11 7 | 22 19 17 11 | 30 26 23 15 | 38 34 29 19 | 60 53 46 30 | 87 76 66 44 | 1/0 2/0 3/0 4/0 | 0 0 0 0 | 1 1 0 0 | 1 1 1 1 | 1 1 1 1 | 2 2 1 1 | 4 4 3 3 | 6 5 4 4 | 10 8 7 6 | 13 11 10 8 | 17 14 12 11 | 26 23 20 17 | 38 33 28 24 | 250 300 350 400 500 | 0 0 0 0 0 | 0 0 0 0 0 | 0 0 0 0 0 | 1 1 1 1 1 | 1 1 1 1 1 | 1 1 1 1 1 | 3 2 2 1 1 | 4 4 4 3 3 | 6 5 5 4 4 | 8 7 6 6 5 | 13 11 10 9 8 | 18 16 15 13 11 |
NOTE
This table is just a portion of table C.8 Apply only for RHH,RHW,RHW-2 MD stands for Metric Designator TS stands for Trade Size
Metric Designator | Trade Size |
12 16 21 27 35 41 53 63 78 91 103 129 155 | 3/8 1/2 3/4 1 1 _ 1/4 1_ 1/2 2 2_ 1/2 3 3_ 1/2 4 5 6 | The metric designators and Trade sizes are for identification purposes only and are not actual dimensions
Apply the table C.8:
If cable type is RHH, or RHW, or RHW-2 Cable size is 14 AWG, then: Maximum 4 cables can be combined in a ½ inch rigid metal conduit size.